zabbix_export: version: '6.0' date: '2023-07-21T11:28:14Z' groups: - uuid: 7df96b18c230490a9a0a9e2307226338 name: Templates templates: - uuid: 36866620c03b442d9886523a575dd3f9 template: 'TOHOST - Module Operators DSE855 Generator - MB2' name: 'TOHOST - Module Operators DSE855 Generator - MB2' groups: - name: Templates items: - uuid: 6e60bf7c84fc49249ed35887a55fe6d9 name: 'Charge Alternator V' key: 'modbus.get[MB2,,3,1028]' units: V description: 'Acionado Somente quando o gerador esta em operacao' tags: - tag: Engine value: Charge - uuid: 1c4061d92db847669c1de2185a2cd638 name: 'Voltage Battery Generator' key: 'modbus.get[MB2,,3,1029]' value_type: FLOAT units: V preprocessing: - type: MULTIPLIER parameters: - '0.1' tags: - tag: Engine value: 'Battery Voltage' - uuid: 89550c7e23b14aad92b51f736606b3c3 name: 'Engine Speed RPM' key: 'modbus.get[MB2,,3,1030]' units: rpm description: 'Contagem somente acionada quando gerador esta acionado.' tags: - tag: Engine value: Speed - uuid: 3396928872da4dd18759aecc0d53c586 name: 'Frequency (Generator)' key: 'modbus.get[MB2,,3,1031]' units: MHz - uuid: 7613873d2e7844d1ba31601914d82bd4 name: 'Voltage L1 to Neutral (Generator)' key: 'modbus.get[MB2,,3,1033]' value_type: FLOAT units: V preprocessing: - type: MULTIPLIER parameters: - '0.1' - uuid: 3960e03a82624e9a99fbf93bd1d768a9 name: 'Voltage L2 to Neutral (Generator)' key: 'modbus.get[MB2,,3,1035]' value_type: FLOAT units: V preprocessing: - type: MULTIPLIER parameters: - '0.1' - uuid: e915b74154c24bcba1602b4536f6a98b name: 'Voltage L3 to Neutral (Generator)' key: 'modbus.get[MB2,,3,1037]' value_type: FLOAT units: V preprocessing: - type: MULTIPLIER parameters: - '0.1' - uuid: a3a0d3a085e948198a37da32b23e7a0b name: 'Voltage Tree-Phase L1 to L2 (Generator)' key: 'modbus.get[MB2,,3,1039]' value_type: FLOAT units: V preprocessing: - type: MULTIPLIER parameters: - '0.1' tags: - tag: Main value: Voltage - uuid: 8ee06de13dca47d2a40eff2968a07119 name: 'Voltage Tree-Phase L2 to L3 (Generator)' key: 'modbus.get[MB2,,3,1041]' value_type: FLOAT units: V preprocessing: - type: MULTIPLIER parameters: - '0.1' tags: - tag: Main value: Voltage - uuid: 1365aea7afe5481ea6db0056e4077106 name: 'Voltage Tree-Phase L3 to L1 (Generator)' key: 'modbus.get[MB2,,3,1043]' value_type: FLOAT units: V preprocessing: - type: MULTIPLIER parameters: - '0.1' tags: - tag: Main value: Voltage - uuid: a58a475501b34ac390a36770ddbe682b name: 'Amper L1 (Generator)' key: 'modbus.get[MB2,,3,1045]' units: A tags: - tag: Generator value: Amper - uuid: e2f70b9d80d94c73a3008df2716d283a name: 'Amper L2 (Generator)' key: 'modbus.get[MB2,,3,1047]' units: A tags: - tag: Generator value: Amper - uuid: 82e4d12946174d8b9c61575833deaac7 name: 'Amper L3 (Generator)' key: 'modbus.get[MB2,,3,1049]' units: A tags: - tag: Generator value: Amper - uuid: d644cede264d4f1fa2f0ae6df61a9cdd name: 'Frequency (Mains)' key: 'modbus.get[MB2,,3,1059]' value_type: FLOAT units: HZ preprocessing: - type: MULTIPLIER parameters: - '0.1' tags: - tag: Main value: Frequency - uuid: 0d24fcb2fd6b4a7a9bc686f2fd7b8548 name: 'Voltage L1 to Neutral (Mains)' key: 'modbus.get[MB2,,3,1061]' value_type: FLOAT units: V preprocessing: - type: MULTIPLIER parameters: - '0.1' tags: - tag: Main value: Voltage - uuid: 8808a2f902c547238f8d4ac0b4cd6af7 name: 'Voltage L2 to Neutral (Mains)' key: 'modbus.get[MB2,,3,1063]' value_type: FLOAT units: V preprocessing: - type: MULTIPLIER parameters: - '0.1' tags: - tag: Main value: Voltage - uuid: 18b342abe100409581b0f2293d4d4351 name: 'Voltage L3 to Neutral (Mains)' key: 'modbus.get[MB2,,3,1065]' value_type: FLOAT units: V preprocessing: - type: MULTIPLIER parameters: - '0.1' tags: - tag: Main value: Voltage - uuid: 792cd38b15fd4f1cae0ab75e26a76a95 name: 'Voltage Tree-Phase L1 to L2 (Mains)' key: 'modbus.get[MB2,,3,1067]' value_type: FLOAT units: V preprocessing: - type: MULTIPLIER parameters: - '0.1' tags: - tag: Main value: Voltage - uuid: b2fe45210a804e249f1653b8f38e3fec name: 'Voltage Tree-Phase L2 to L3 (Mains)' key: 'modbus.get[MB2,,3,1069]' value_type: FLOAT units: V preprocessing: - type: MULTIPLIER parameters: - '0.1' tags: - tag: Main value: Voltage - uuid: 8de3bc54a1984a05982a44ef370dfeb8 name: 'Voltage Tree-Phase L3 to L1(Mains)' key: 'modbus.get[MB2,,3,1071]' value_type: FLOAT units: V preprocessing: - type: MULTIPLIER parameters: - '0.1' tags: - tag: Main value: Voltage - uuid: e66641fe2b3946578f0065ee9a2a2a08 name: 'kVA L1 (POWER)' key: 'modbus.get[MB2,,3,1539]' description: 'Medicao disponivel apenas no modo acionado.' tags: - tag: Power value: kVA - uuid: 71c6595a1d0b4501a4d19294ebc24261 name: 'kVA L2 (POWER)' key: 'modbus.get[MB2,,3,1541]' description: 'Medicao disponivel apenas no modo acionado.' tags: - tag: Power value: kVA - uuid: 7c054f976fc5450c93ccb92b85ab4cb3 name: 'kVA L3 (POWER)' key: 'modbus.get[MB2,,3,1543]' description: 'Medicao disponivel apenas no modo acionado.' tags: - tag: Power value: kVA - uuid: cca343d5081b4866a720543099480b4a name: 'kVA TOTAL (POWER)' key: 'modbus.get[MB2,,3,1545]' description: 'Medicao disponivel apenas no modo acionado.' tags: - tag: Power value: kVA - uuid: 69b49c18d3404552903ba936eb093f6b name: 'kVAr L1 (POWER)' key: 'modbus.get[MB2,,3,1547]' value_type: FLOAT description: 'POTENCIA REATIVA kVAr é a potencia armazenada e devolvida (quilovolt ampere reativo)' preprocessing: - type: MULTIPLIER parameters: - '0.1' tags: - tag: Power value: kVAr - uuid: 4dcdab951a6b44cea8c3bf36069efe08 name: 'kVAr L2 (POWER)' key: 'modbus.get[MB2,,3,1549]' value_type: FLOAT description: 'POTENCIA REATIVA kVAr é a potencia armazenada e devolvida (quilovolt ampere reativo)' preprocessing: - type: MULTIPLIER parameters: - '0.1' tags: - tag: Power value: kVAr - uuid: 80860919c5904a5796374ee1f9a7671f name: 'kVAr L3 (POWER)' key: 'modbus.get[MB2,,3,1551]' value_type: FLOAT description: 'POTENCIA REATIVA kVAr é a potencia armazenada e devolvida (quilovolt ampere reativo)' preprocessing: - type: MULTIPLIER parameters: - '0.1' tags: - tag: Power value: kVAr - uuid: 27cec3d406af4cc7b8360011d02dcf30 name: 'kVAr TOTAL (POWER)' key: 'modbus.get[MB2,,3,1553]' units: kVAr description: 'POTENCIA REATIVA kVAr é a potencia armazenada e devolvida (quilovolt ampere reativo)' tags: - tag: Power value: kVAr - uuid: d475f357ef9e4ce3834deff1fcc33e2e name: 'Power Factor L1 (Power)' key: 'modbus.get[MB2,,3,1554]' value_type: FLOAT preprocessing: - type: MULTIPLIER parameters: - '0.1' - uuid: 2daac6130cac4da2881d02575937db7a name: 'Power Factor L2 (Power)' key: 'modbus.get[MB2,,3,1555]' value_type: FLOAT preprocessing: - type: MULTIPLIER parameters: - '0.1' - uuid: bbff2655797c452dbe59e4345adbb647 name: 'Power Factor L3 (Power)' key: 'modbus.get[MB2,,3,1556]' value_type: FLOAT preprocessing: - type: MULTIPLIER parameters: - '0.1' - uuid: 5d03b7f116224d2caa536e9e85bcee55 name: 'Power Factor TOTAL (Power)' key: 'modbus.get[MB2,,3,1557]' value_type: FLOAT preprocessing: - type: MULTIPLIER parameters: - '0.1' - uuid: 85d5d634494b4291ad551363d6788884 name: 'KiloWatt hour (kWh)' key: 'modbus.get[MB2,,3,1801]' delay: 1h history: 30d trends: 90d value_type: FLOAT units: kWh description: 'A kWh represents the amount of energy consumed by a load with a power of one thousand watts for a duration of one hour.' preprocessing: - type: MULTIPLIER parameters: - '0.1' tags: - tag: General value: Accumulated - uuid: bac238b6805b4eebb07466563750ba86 name: 'KiloVolt Ampere hours (kVAh)' key: 'modbus.get[MB2,,3,1805]' delay: 1h history: 30d trends: 90d value_type: FLOAT units: kVAh preprocessing: - type: MULTIPLIER parameters: - '0.1' tags: - tag: General value: Accumulated - uuid: 78d032c21ce3461aa951f866355f7063 name: 'KiloVolt Ampere Reactive hour (kVArh)' key: 'modbus.get[MB2,,3,1807]' delay: 1h history: 30d trends: 90d value_type: FLOAT units: kVArh description: 'Energy Reactive' preprocessing: - type: MULTIPLIER parameters: - '0.1' tags: - tag: General value: Accumulated - uuid: 9ab4e66c8383420387267d68d8798100 name: 'Engine Starts' key: 'modbus.get[MB2,,3,1809]' description: 'The quantity generator engine has been started.' tags: - tag: Engine value: Started - uuid: 36c946ccfb214168b8c0f625d275fd1f name: 'FUEL %' key: 'modbus.get[MB22,,3,1027]' value_type: FLOAT units: '%' tags: - tag: Generator value: Engine triggers: - uuid: e0a025e16a294080ac82f3f8a360d379 expression: 'last(/TOHOST - Module Operators DSE855 Generator - MB2/modbus.get[MB22,,3,1027])<20' name: 'FUEL BELOW 20%' priority: HIGH - uuid: b41f70d25c8940e4bdbb336b1d3b1025 expression: 'last(/TOHOST - Module Operators DSE855 Generator - MB2/modbus.get[MB22,,3,1027])<25' name: 'INFO FUEL BELOW 25%' priority: WARNING macros: - macro: '{$MODBUS.PORT}' value: '502' triggers: - uuid: 1b5e8663fcd747deac7a2336cf309451 expression: | last(/TOHOST - Module Operators DSE855 Generator - MB2/modbus.get[MB2,,3,1039])>0 or last(/TOHOST - Module Operators DSE855 Generator - MB2/modbus.get[MB2,,3,1041])>0 or last(/TOHOST - Module Operators DSE855 Generator - MB2/modbus.get[MB2,,3,1043])>0 name: 'ON MODE GENERATOR' priority: HIGH - uuid: acbda1c107c2495f961249e8d81dddaf expression: | last(/TOHOST - Module Operators DSE855 Generator - MB2/modbus.get[MB2,,3,1067])=0 or last(/TOHOST - Module Operators DSE855 Generator - MB2/modbus.get[MB2,,3,1069])=0 or last(/TOHOST - Module Operators DSE855 Generator - MB2/modbus.get[MB2,,3,1071])=0 name: 'ZERO Voltage Input (FALHA ELETRICA)' priority: DISASTER